Equipment goods
CZ3000 Temperature Converter Signal Conditioner |
|
CZ3076 |
CZ3079 |
|
CZ3071 |
1/2 |
2/2 |
|
1/1 |
|
|
|
Input Signal |
Pt100,Cu100,Cu50 |
Pt100,Cu100,Cu50 |
Pt100,Cu100,Cu50 |
Output Current/Load Resistance |
0~20mA,4~20mA / RL ≤300Ω |
0~20mA,4~20mA / RL ≤300Ω |
0~20mA,4~20mA / RL ≤300Ω |
Output Voltage/Load Resistance |
0~5V,1~5V / RL ≥20kΩ |
0~5V,1~5V / RL ≥20kΩ |
0~5V,1~5V / RL ≥20kΩ |
Fault Current of Overrange/Underrange |
IH≈20.8mA/IL≈3.8mA |
IH≈20.8mA/IL≈3.8mA |
IH≈20.8mA/IL≈3.8mA |
Fault Current of Line Break |
I≈20.8mA |
I≈20.8mA |
I≈20.8mA |
Supply Voltage |
20~35V DC |
20~35V DC |
20~35V DC |
Power Reverse Protection |
Support |
Support |
Support |
Current Consumption(Supply voltage: 24V) |
≤35mA |
≤55mA |
≤55mA |
Temperature Drift |
0.01%F.S./℃ |
0.01%F.S./℃ |
0.01%F.S./℃ |
Response Time (0~90%) |
≤1s |
≤1s |
≤1s |
Dielectric Strength |
1500V AC;1min |
1500V AC;1min |
1500V AC;1min |
Insulation Resistance |
≥100MΩ; 500V DC |
≥100MΩ; 500V DC |
≥100MΩ; 500V DC |
EMC Standards |
GB/T 18268(IEC 61326-1) |
GB/T 18268(IEC 61326-1) |
GB/T 18268(IEC 61326-1) |
Ambient Temperature |
-20℃~+60℃ |
-20℃~+60℃ |
-20℃~+60℃ |
Suitable Field Apparatus |
2-or 3-wire RTD |
2-or 3-wire RTD |
2-or 3-wire RTD |
|
|
|
|
|
CZ3072 |
CZ3074 |
CZ3079.TC |
1/1 |
1/2 |
2/2 |
|
Input Signal(Customized mV signal) |
T、E、J、K、N、R、S、B |
T、E、J、K、N、R、S、B |
T、E、J、K、N、R、S、B |
Internal CJC Temperature Range |
-20℃~+60℃ |
-20℃~+60℃ |
-20℃~+60℃ |
CJC Precision |
±1℃ |
±1℃ |
±1℃ |
Output Current/Load Resistance |
0~20mA,4~20mA / RL≤300Ω |
0~20mA,4~20mA / RL≤300Ω |
0~20mA,4~20mA / RL≤300Ω |
Output Voltage/Load Resistance |
0~5V,1~5V / RL ≥20kΩ |
0~5V,1~5V / RL ≥20kΩ |
0~5V,1~5V / RL ≥20kΩ |
Fault Current of Overrange/Underrange |
IH≈20.8mA/IL ≈3.8mA |
IH≈20.8mA/IL ≈3.8mA |
IH≈20.8mA/IL ≈3.8mA |
Fault Current of Line Break |
I≈20.8mA |
I≈20.8mA |
I≈20.8mA |
Supply Voltage |
20~35V DC |
20~35V DC |
20~35V DC |
Power Reverse Protection |
Support |
Support |
Support |
Current Consumption(Supply voltage: 24V) |
≤35mA |
≤55mA |
≤55mA |
Temperature Drift |
0.01%F.S./℃ |
0.01%F.S./℃ |
0.01%F.S./℃ |
Response Time (0~90%) |
≤1s |
≤1s |
≤1s |
Dielectric Strength |
1500V AC;1min |
1500V AC;1min |
1500V AC;1min |
Insulation Resistance |
≥100MΩ; 500V DC |
≥100MΩ; 500V DC |
≥100MΩ; 500V DC |
EMC Standards |
GB/T 18268(IEC 61326-1) |
GB/T 18268(IEC 61326-1) |
GB/T 18268(IEC 61326-1) |
Ambient Temperature |
-20℃~+60℃ |
-20℃~+60℃ |
-20℃~+60℃ |
Suitable Field Apparatus |
TC and mV signal sensor |
TC and mV signal sensor |
TC and mV signal sensor |
|
|
|
|
|
1/1:CZ3077 |
1/1:CZ3177 |
1/1:CZ3277 |
2/2:CZ3078 |
2/2:CZ3178 |
2/2:CZ3278 |
|
Input Signal |
Pt100,Cu100,Cu50 |
T、E、J、K、N、R、S、B |
Pt100,Cu100,Cu50 |
(Customized mV signal) |
T、E、J、K、N、R、S、B |
||
Internal CJC Temperature Range |
|
-20~+60℃ |
-20~+60℃ |
CJC Precision |
|
±1℃ |
±1℃ |
Output Current |
4~20mA |
4~20mA |
4~20mA |
Load Resistance |
RL ≤(Ue -12)/0.021Ω |
RL ≤(Ue -12)/0.021Ω |
RL ≤(Ue -12)/0.021Ω |
Fault Current of Overrange/Underrange |
IL ≈20.8mA/IL ≈3.8mA |
IL ≈20.8mA/IL ≈3.8mA |
IL ≈20.8mA/IL ≈3.8mA |
Fault Current of Line Break |
I≈20.8mA |
I≈20.8mA |
I≈20.8mA |
Loop Supply Voltage(Ue) |
12~30V DC |
12~30V DC |
12~30V DC |
Power Reverse Protection |
Support |
Support |
Support |
Temperature Drift |
0.01%F.S./℃ |
0.01%F.S./℃ |
0.01%F.S./℃ |
Response Time (0~90%) |
≤1s |
≤1s |
≤1s |
Dielectric Strength |
1500V AC;1min |
1500V AC;1min |
1500V AC;1min |
Insulation Resistance |
≥100MΩ; 500V DC |
≥100MΩ; 500V DC |
≥100MΩ; 500V DC |
EMC Standards |
GB/T 18268(IEC 61326-1) |
GB/T 18268(IEC 61326-1) |
GB/T 18268(IEC 61326-1) |
Ambient Temperature |
-20℃~+60℃ |
-20℃~+60℃ |
-20℃~+60℃ |
Suitable Field Apparatus |
2-or 3-wire RTD |
TC sensor,mV signal |
RTD,TC sensor |
Signal conditioners are electrical devices, which are connected between the industrial field instrument and the control room. CHENZHU's signal conditioner complete in specifications.
Good deal: buying from seller
This page is about importers and exporters of CZ3000 Temperature Converter Signal Conditioner Search in a category : Equipment goods Search in a category : temperature, conditioner, converter, cz3000, signal |
Tuesday, June 16, 2015
Quantity : 100 roll
JC-Paper Series Refractory ceramic fiber paper sealing gasket Product Features Easy to cut,wrap or form Low thermal conductivity and heat storage Excellent thermal shock and flame resistance Light weight Resilient Excellent hydrophobic property Good dielectric strength Free...
Sunday, May 29, 2016
Quantity : 90
- Avantages des luminaires LED OSRAM - - Qualité OSRAM - Produits LED de haute qualité pour les demandes exigeantes - Remplacement direct des luminaires conventionnels fluorescents ou halogènes - Le remplacement des luminaires standard permet jusqu'à 85 % d'économie d'énergie...
Thursday, December 17, 2015
Quantity : 5000 tons - Price : 90EUR
We are direct manufacturer and main supplier of European standard Wood Pellet 6mm, 8mm with Moisture content: <7% and Calorific value: <4.7kWh/kg.<br /> SPECIFICATION FOR WOOD PELLETS: 1. Application: House Heating 2. Made From: Compacted Sawdust 3. Shape: Stick 4...